Yayın:
Parametric study and thermal sensitivity analysis of a triple effect absorption refrigeration system

Küçük Resim

Akademik Birimler

Kurum Yazarları

Yazarlar

Saka, Kenan
Orhan, Mehmet Fatih

Danışman

Dil

Türü

Yayıncı:

Elsevier

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Özet

Absorption refrigeration systems represent an efficient means of cooling utilizing waste heat, with triple-effect absorption refrigeration systems outperforming their double and single-effect counterparts in terms of efficiency. This study conducts energy and exergy analyses on a triple-effect absorption refrigeration system, focusing on internal heat balance and thermal sensitivity to maximize efficiency. The analysis pinpointed the most sensitive thermal sensitivity areas within the system, highlighting the high-pressure condenser (HPC) outlet and medium-pressure condenser (MPC) outlet as critical points. Notably, increasing the temperatures of HPC and MPC leads to enhanced COP and ECOP, with a mere 5 K rise in HPC exit temperature resulting in a remarkable 57 % boost in system performance. Similarly, elevating the MPC operating temperature by 5 K yields a significant 34 % improvement in COP value.

Açıklama

Kaynak:

Anahtar Kelimeler:

Konusu

Single, Cycle, Optimization, Triple effect absorption refrigeration system, Series flow, Energy analysis, Exergy, Internal condensers, Thermodynamics, Physical sciences, Science & Technology

Alıntı

Endorsement

Review

Supplemented By

Referenced By

0

Views

3

Downloads

View PlumX Details