Theoretical study on the effect of operating conditions on performance of absorption refrigeration system

dc.contributor.buuauthorKaynaklı, Ömer
dc.contributor.buuauthorKılıç, Muhsin
dc.contributor.departmentUludağ Üniversitesi/Mühendislik Fakültesi/Makina Mühendisliği Bölümü.tr_TR
dc.contributor.orcid0000-0003-2113-4510tr_TR
dc.contributor.researcheridO-2253-2015tr_TR
dc.contributor.scopusid8387145900tr_TR
dc.contributor.scopusid57202677637tr_TR
dc.date.accessioned2021-09-15T13:33:38Z
dc.date.available2021-09-15T13:33:38Z
dc.date.issued2007
dc.description.abstractIn this study, a detailed thermodynamic analysis of the water/lithium bromide absorption refrigeration cycle is performed. The influences of operating temperature and effectiveness of heat exchanger on the thermal loads of components, coefficients of performance (COPc, COP) and efficiency ratio (eta) are investigated. It is concluded that the COPc and COP values increase with increasing generator and evaporator temperatures but decrease with increasing condenser and absorber temperatures. The eta value varies with these temperatures. Also, the effects of solution and refrigerant heat exchangers on the performance, efficiency ratio of the system and fluid temperatures are compared. As a result, it is found that the solution heat exchanger (SHE) has more effect on the investigated parameters than the refrigerant heat exchanger (RHE). While the SHE increases the COP value up to a maximum 44%, the RHE has an effect of only 2.8%.en_US
dc.identifier.citationKaynaklı, O ve Kılıç, M. (2007). "Theoretical study on the effect of operating conditions on performance of absorption refrigeration system". Energy Conversion and Management, 48(2), 599-607.en_US
dc.identifier.endpage607tr_TR
dc.identifier.issn01968904
dc.identifier.issue2tr_TR
dc.identifier.scopus2-s2.0-33845864720tr_TR
dc.identifier.startpage599tr_TR
dc.identifier.urihttps://doi.org/10.1016/j.enconman.2006.06.005
dc.identifier.urihttps://www.sciencedirect.com/science/article/pii/S0196890406001920
dc.identifier.urihttp://hdl.handle.net/11452/21974
dc.identifier.volume48tr_TR
dc.identifier.wos000243799500031tr_TR
dc.indexed.scopusScopusen_US
dc.indexed.wosSCIEen_US
dc.language.isoenen_US
dc.publisherPergamon-Elsevier Scienceen_US
dc.relation.journalEnergy Conversion and Managementen_US
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergitr_TR
dc.rightsinfo:eu-repo/semantics/closedAccessen_US
dc.subjectAbsorptionen_US
dc.subjectRefrigerationen_US
dc.subjectWater/lithium bromideen_US
dc.subjectAqueous ternary hydroxideen_US
dc.subjectAmbient-temperatureen_US
dc.subjectCycleen_US
dc.subjectOptimizationen_US
dc.subjectSimulationen_US
dc.subjectEnergyen_US
dc.subjectEvaporationen_US
dc.subjectFluid dynamicsen_US
dc.subjectHeat exchangersen_US
dc.subjectLithium compoundsen_US
dc.subjectThermodynamicsen_US
dc.subjectEfficiency ratioen_US
dc.subjectSolution heat exchanger (SHE)en_US
dc.subject.scopusAbsorption Refrigeration; Solar Cooling; Lithium Bromideen_US
dc.subject.wosThermodynamicsen_US
dc.subject.wosEnergy & fuelsen_US
dc.subject.wosMechanicsen_US
dc.titleTheoretical study on the effect of operating conditions on performance of absorption refrigeration systemen_US
dc.typeArticle
dc.wos.quartileQ2en_US
dc.wos.quartileQ1 (Mechanics)en_US

Files

License bundle
Now showing 1 - 1 of 1
Name:
license.txt
Size:
1.71 KB
Format:
Item-specific license agreed upon to submission
Description: